Al Sanaya Technical Equipment L.L.C
Engineering

Earthing and bonding for busbar trunking systems

A busduct run is only as safe as its earth path. How earthing and bonding work in busbar trunking, the role of the housing, and what to verify on site.

Al Sanaya Engineering

·7 min read

Busbar trunking joint sets and earth-continuity detail

Everyone scrutinises a busduct's current rating. Far fewer give the earth path the same attention — yet on a fault, that earth path is what carries the fault current home, operates the protective device, and keeps the housing from becoming live. This article explains how earthing and bonding work in busbar trunking and what to check on site.

Earthing vs bonding

The two terms are often used loosely, but they do different jobs. Earthing provides a low-impedance return path so fault current flows back to the source and trips the protective device fast. Bonding ties metal parts together so they stay at the same potential — nobody touching two bonded surfaces during a fault sees a dangerous voltage between them.

A busduct system relies on both: a proven earth path along its length, and bonding to the building's earthing system and to adjacent metalwork.

The earth path inside the busduct

Sandwich-type busbar trunking handles the protective earth in one of two ways: the metal housing itself is rated as the PE conductor, or a dedicated earth bar runs alongside the phase bars — frequently both.

What matters is that the manufacturer declares the earth path's effective cross-section and its short-time withstand rating, verified by type test to IEC 61439-6. An earth path that is adequate for a small feeder may be undersized for a 4000 A rising main with a high prospective fault current.

Joints — the weak link

A busduct earth path is not continuous metal; it is a chain of bolted joints. Every joint is a potential weak point. An under-torqued bolt, a missing washer, paint left under a contact face or corrosion over time all raise the joint's resistance.

Raise enough joint resistances and the earth-loop impedance climbs until the protective device no longer disconnects within the required time. That is why joint torque and earth continuity are inspection items, not afterthoughts.

What to verify on site

  • Joint bolts tightened to the manufacturer's specified torque
  • Contact faces clean — no paint, oxide or debris
  • Earth continuity measured across every joint and end to end
  • Busduct bonded to the building earth at the declared points
  • Measured fault-loop impedance compared against the design figure

Fault-loop impedance

The proof of a sound earthing arrangement is the measured fault-loop impedance. It must be low enough that, on an earth fault, the protective device disconnects within the time the wiring regulations and IEC 60364 require. Measuring it at the far end of the run — and comparing it with the design calculation — confirms the whole earth path, joints included, is doing its job.

How Al Sanaya can help

We engineer and install Linkk and Megaduct busduct across the GCC and MENA, and our scope includes verified joint torque, earth continuity testing at every joint, and documented fault-loop impedance measurements as part of handover.

?

Frequently asked questions

Does the busduct housing act as the earth conductor?

In many sandwich-type systems the metal housing is designed and rated as the protective earth (PE) path, often supplemented by an integral earth bar. The key point is that the manufacturer must declare and test the earth path's cross-section and fault rating — it cannot be assumed.

What is the difference between earthing and bonding?

Earthing connects the system to the general mass of earth, giving fault current a path back to the source so protection operates. Bonding connects exposed and extraneous metal parts together so they sit at the same potential, preventing dangerous voltage differences during a fault.

Why is earth continuity tested at every joint?

A busduct earth path is made up of many bolted joints. A single under-torqued or corroded joint raises the earth-loop impedance and can stop protection from clearing a fault quickly. Testing continuity across every joint confirms the path is sound end to end.

What standard covers busbar trunking earthing?

IEC 61439-6 covers busbar trunking systems, including the protective earth requirements. The connected installation is then designed and verified to the local wiring regulations and IEC 60364 for fault-loop impedance and disconnection times.

Tags

#earthing busbar trunking#busduct earthing#bonding busway#busbar trunking earth continuity#integral earth busduct#separate earth conductor#IEC 61439-6 earthing#fault loop impedance busduct